No image published for this recall
Legrand Residual Current Circuit Breaker (safety switch): RX3 RCCB 63A 30mA Type A 2P - sold through trade channels
Official notice
21 Jul 2026
Last checked
21 Jul 2026
An official Product Safety NZ notice concerns Legrand Residual Current Circuit Breaker (safety switch): RX3 RCCB 63A 30mA Type A 2P - sold through trade channels. Legrand is recalling the Residual Current Circuit Breaker (safety switch): RX3 RCCB 63A 30mA Type A 2P because of a risk of electric shock and electrocution. An affected unit may fail to trip in response to certain types of fault current (specifically, pulsating DC residual currents), meaning it may not provide the level of electrocution protection indicated by its markings. This is due to a mixed-batch manufacturing issue. Affected units are internally coded as 100mA Type AC rather than 30mA Type A as marked, providing tripping only for residual sinusoidal alternating current, not for residual pulsating DC currents as required. Published 2026-07-21.
What to do now
Electrical professionals should test with an external RCD tester — this is the only reliable field method for confirming whether a unit is affected. Do not use the integrated test button. A faulty unit will fail to trip at 30mA when tested with an external RCD tester. Ensure the test settings are set to 30mA type A. If you are uncertain whether a unit is affected, treat it as affected. If your unit is affected, contact Legrand and let them know. Once they have identified the full extent of affected units through distributor and installer records and responses to the public Recall Notice, Legrand will collect all potentially affected units and provide replacements at its own cost. The remedy is a free replacement of affected units.
Official notice
2026-07-21
The hazard
The hazard
Legrand is recalling the Residual Current Circuit Breaker (safety switch): RX3 RCCB 63A 30mA Type A 2P because of a risk of electric shock and electrocution. An affected unit may fail to trip in response to certain types of fault current (specifically, pulsating DC residual currents), meaning it may not provide the level of electrocution protection indicated by its markings. This is due to a mixed-batch manufacturing issue. Affected units are internally coded as 100mA Type AC rather than 30mA Type A as marked, providing tripping only for residual sinusoidal alternating current, not for residual pulsating DC currents as required.
How to check if you're affected
How to check if you're affected
Compare the product name and identifiers below with the item you own. Follow the official notice if they match.
Lots
Checked manually this time?
The app alerts you when a new official recall is published — no searching, no checking back.
Turn on recall alertsAffected products
Affected products
Product 1
Risk / hazard
Where it was sold
Where it was sold
The source does not list specific retailers. See the official notice for where affected products were sold.
Location 1
Affected area 1
Company & contacts
Company & contacts
Manufacturer
Phone
Brand: Legrand Residual Current Circuit Breaker Rx3 Rccb 63a 30ma Type A 2p. Contact: Legrand New Zealand. Phone 0800 476 009.
Source & status
Source & status
Recall details
Recall details
Classification
Source tier
Documents, notices & source
See the official notice and source documents for full details.
View full official noticeRelated recalls
Weekly recall digest
Get next week's recalls before you need them.
One email every Monday — official-source recalls for your country, and nothing else. Unsubscribe from any email.
The digest is the slow lane — one email a week. For instant, severity-gated alerts the moment a notice is published, get the app.
This recall was published 21 Jul 2026. The next one won't wait for you to search.
RecallScope watches official sources for the brands and VINs you follow, and alerts you the moment a new notice is published.