Legrand Residual Current Circuit Breaker (safety switch): RX3 RCCB 63A 30mA Type A 2P - sold through trade channels

Official notice

21 Jul 2026

Last checked

21 Jul 2026

An official Product Safety NZ notice concerns Legrand Residual Current Circuit Breaker (safety switch): RX3 RCCB 63A 30mA Type A 2P - sold through trade channels. Legrand is recalling the Residual Current Circuit Breaker (safety switch): RX3 RCCB 63A 30mA Type A 2P because of a risk of electric shock and electrocution. An affected unit may fail to trip in response to certain types of fault current (specifically, pulsating DC residual currents), meaning it may not provide the level of electrocution protection indicated by its markings. This is due to a mixed-batch manufacturing issue. Affected units are internally coded as 100mA Type AC rather than 30mA Type A as marked, providing tripping only for residual sinusoidal alternating current, not for residual pulsating DC currents as required. Published 2026-07-21.

What to do now

Electrical professionals should test with an external RCD tester — this is the only reliable field method for confirming whether a unit is affected. Do not use the integrated test button. A faulty unit will fail to trip at 30mA when tested with an external RCD tester. Ensure the test settings are set to 30mA type A. If you are uncertain whether a unit is affected, treat it as affected. If your unit is affected, contact Legrand and let them know. Once they have identified the full extent of affected units through distributor and installer records and responses to the public Recall Notice, Legrand will collect all potentially affected units and provide replacements at its own cost. The remedy is a free replacement of affected units.

Official notice

2026-07-21

The hazard

Legrand is recalling the Residual Current Circuit Breaker (safety switch): RX3 RCCB 63A 30mA Type A 2P because of a risk of electric shock and electrocution. An affected unit may fail to trip in response to certain types of fault current (specifically, pulsating DC residual currents), meaning it may not provide the level of electrocution protection indicated by its markings. This is due to a mixed-batch manufacturing issue. Affected units are internally coded as 100mA Type AC rather than 30mA Type A as marked, providing tripping only for residual sinusoidal alternating current, not for residual pulsating DC currents as required.

How to check if you're affected

Compare the product name and identifiers below with the item you own. Follow the official notice if they match.

Lots

manufacturing, Date, marking

Checked manually this time?

The app alerts you when a new official recall is published — no searching, no checking back.

Turn on recall alerts

Affected products

Product 1

Legrand Residual Current Circuit Breaker (safety switch): Legrand, RX3 RCCB 63A 30mA Type A 2P Product Code: LG-402038 Batch Date Code: 24W24 The batch marking (24W24) appears on the left side panel of the unit. The product detail markings on the rear of the unit further indicate whether it is from the affected batch. On the packaging, look for batch date code 24W24 on the product box without a green dot — if a green dot is present, the product has been checked and the unit is not faulty. Sold via Trade channel distributors and licensed electrical installers from 17 December 2024 to 15 June 2026.

Risk / hazard

Legrand is recalling the Residual Current Circuit Breaker (safety switch): RX3 RCCB 63A 30mA Type A 2P because of a risk of electric shock and electrocution. An affected unit may fail to trip in response to certain types of fault current (specifically, pulsating DC residual currents), meaning it may not provide the level of electrocution protection indicated by its markings. This is due to a mixed-batch manufacturing issue. Affected units are internally coded as 100mA Type AC rather than 30mA Type A as marked, providing tripping only for residual sinusoidal alternating current, not for residual pulsating DC currents as required.

Where it was sold

The source does not list specific retailers. See the official notice for where affected products were sold.

Location 1

NZ · New Zealand

Affected area 1

NZ · New Zealand

Company & contacts

Manufacturer

Not provided

Phone

0800 476 009

Brand: Legrand Residual Current Circuit Breaker Rx3 Rccb 63a 30ma Type A 2p. Contact: Legrand New Zealand. Phone 0800 476 009.

Source & status

Tier

official

Category

ELECTRONICS

Classification

Product recall

App estimate

high

Recall details

Classification

Product recall

Source tier

official

Documents, notices & source

See the official notice and source documents for full details.

View full official notice
Something wrong on this page?

Related recalls

NZ
No image published for this recall

Living & Co Fan Heater and Fan Heater with Oscillation 2000W - Sold at The Warehouse

High riskProduct Safety NZ4 Sept 2026

Weekly recall digest

Get next week's recalls before you need them.

One email every Monday — official-source recalls for your country, and nothing else. Unsubscribe from any email.

The digest is the slow lane — one email a week. For instant, severity-gated alerts the moment a notice is published, get the app.

This recall was published 21 Jul 2026. The next one won't wait for you to search.

RecallScope watches official sources for the brands and VINs you follow, and alerts you the moment a new notice is published.